Model | ||
product brand name | SENTRON | |
product designation | RCCB | |
design of the product | Instantaneous | |
General technical data | ||
number of poles | 4 | |
size of installation devices / acc. to DIN 43880 | 1 | |
mechanical service life (switching cycles) / typical | 2 000 | |
short-circuit current / of series fuse / maximum permissible | 100 A | |
short-circuit current rating | 6 kA | |
switching function / short-term delayed | No | |
overvoltage category | III | |
Supply voltage | ||
supply voltage | ||
● at AC / rated value | 400 V | |
● for testing equipment / minimum | 100 V | |
operating frequency | 60 Hz | |
supply voltage frequency / rated value | 60 Hz | |
Protection class | ||
protection class IP | IP20, if the distribution board is installed, with connected conductors | |
Switching capacity | ||
switching capacity current | ||
● acc. to EN 60898 / rated value | 0.8 kA | |
● according to IEC 61008-1 / rated value | 0.8 kA | |
Dissipation | ||
power loss [W] | ||
● for rated value of the current / at AC / in hot operating state / per pole | 3.9 W | |
● maximum | 11.7 W | |
Current | ||
tripping fault current / rated value | 30 mA | |
operational current | ||
● at 40 °C / rated value | 63 A | |
● at AC / rated value | 63 A | |
residual current type | AC | |
let-through current / permissible | 7 100 kA | |
I2t value / permissible | 110 000 A²·s | |
Product details | ||
product feature / silicon-free | Yes | |
product extension / installable / supplementary devices | No | |
Connections | ||
connectable conductor cross-section / solid | ||
● minimum | 0.75 mm² | |
● maximum | 35 mm² | |
connectable conductor cross-section / stranded | ||
● minimum | 0.75 mm² | |
● maximum | 35 mm² | |
tightening torque / with screw-type terminals | ||
● minimum | 2.5 N·m | |
● maximum | 3 N·m | |
position / of power supply cord | top or bottom | |
Mechanical Design | ||
height | 90 mm | |
width | 72 mm | |
depth | 70 mm | |
installation depth | 70 mm | |
number of modular width units | 4 | |
fastening method | DIN rail (REG) | |
mounting position | any | |
net weight | 392 g | |
Environmental conditions | ||
ambient temperature / during operation | ||
● minimum | -25 °C | |
● maximum | 45 °C | |
ambient temperature / during storage | ||
● minimum permissible | -40 °C | |
● maximum permissible | 75 °C | |
number of test cycles / for environmental testing / acc. to IEC 60068-2-30 | 28 |
Peso | 0,392 kg |
---|---|
Dimensões | 7,2 × 7,0 × 9,0 cm |
Apenas clientes logados que compraram este produto podem deixar uma avaliação.
Avaliações
Não há avaliações ainda.